Upper Explosive Limit (UEL) is the maximum concentration of a flammable gas, vapor, or dust in air above which the mixture is too “rich” in fuel and lacks sufficient oxygen to support ignition, propagate a flame or explosion. Above this concentration, the fuel-to-oxygen ratio is outside the combustible range.
Brief Explanation of the Term “Upper Explosive Limit”
The UEL, along with the LEL (Lower Explosive Limit), defines the entire flammable range (or explosive range) of a substance. Understanding the UEL is just as critical as understanding the LEL for ensuring safety in environments where flammable materials are present.
Here’s a breakdown of its significance:
- Below the LEL: The mixture is too lean (not enough fuel).
- Above the UEL: The mixture is too rich (not enough oxygen).
- The UEL is expressed as a percentage (%) of the gas or vapor in air.
- Flammability Range Boundary: The UEL marks the upper boundary of the flammable range. Any concentration between the LEL and the UEL is considered hazardous because it can ignite and burn or explode if an ignition source is introduced.
- “Too Rich” Condition: When the concentration of a flammable substance is above the UEL, the mixture is considered “too rich”. This means there is an excess of fuel relative to the amount of oxygen available in the air. Without sufficient oxygen, combustion cannot be sustained, and therefore, an explosion or fire will not occur.
- The Hidden Hazard of Dilution: It is extremely important to remember that a concentration above the UEL does not mean a space is inherently safe. If the concentration of the flammable substance begins to decrease (e.g., due to ventilation, dilution, or natural dispersion), it will eventually pass down through the flammable range (between the UEL and LEL) before becoming too lean to ignite. During this critical transition, if an ignition source is present, an explosion or fire can readily occur. This is a primary reason why confined space entry procedures often require purging with inert gas before introducing air, or continuous monitoring during ventilation processes.
This is important for assessing fire and explosion hazards in confined spaces, tanks, or industrial environments where flammable substances are present. Even though a mixture above the UEL won’t ignite under normal conditions, it remains extremely dangerous — any drop in concentration into the explosive range can create a highly flammable atmosphere.
UEL stands for Upper Explosive Limit (also called the Upper Flammable Limit, UFL).
Example:
Imagine a tank that has just been emptied of liquid propane but still contains a high concentration of propane vapor, perhaps 15% by volume. This is above the UEL (9.5%), meaning it’s currently too rich to explode.
However, if workers try to ventilate this tank by simply opening hatches and allowing fresh air in, the concentration of propane vapor will start to decrease. As it drops from 15% through 10% and down to, say, 5%, it passes directly through the flammable range (2.1% – 9.5%). If an ignition source (like a static spark from clothing, a tool striking the tank, or even a non-intrinsically safe light) is present during this dilution process, a severe explosion or fire could occur.
Therefore, safe practice dictates that such a tank should be purged with an inert gas (like nitrogen) to displace the flammable vapor and create a non-combustible atmosphere before introducing air, thereby avoiding the dangerous passage through the flammable range.
The UEL of Propane (C₃H₈) is about 9.5% by volume in air.
- LEL: 2.1%
- UEL: 9.5%
- Flammable Range: 2.1%–9.5%
Scenario:
- If propane concentration in a storage tank is 1% → Below LEL (safe, won’t ignite).
- If propane reaches 5% → Within flammable range (EXTREMELY HAZARDOUS if ignition occurs).
- If propane exceeds 10% → Above UEL (too rich to burn, but still dangerous due to oxygen displacement).
Therefore, both LEL and UEL values are critical in monitoring gas concentrations to maintain a safe working environment.